Features
System setup
|
OperationThe air flow monitoring system measures the air flow based on different transmission times of ultrasonic pulses sent in one or the other direction. This cross section measurement delivers the average air speed more reliable and mean-ingful than methods that measure only one or two points on the tunnel wall. Two sensors are mounted below the tunnel ceiling, cross section with an angle of 30° to 60° (usually 45°) such that a vector component of the air flow overlaps the direction of the ultrasonic sound pulses exchanged by the two sensors. Air flow in the tunnel influences the transition time of the pulses be-tween sender and receiver. Based on the difference in transition times of ultrasonic pulses sent in one or the other direction the measured values are calculated. Measured values are air speed, air flow rate, direction of air flow and air temperature. Advantanges
|
ApplicationTunnels are important infrastructure elements in road networks and facilitate the connection of regions. Environmental conditions in tunnels are influenced by fog, particles and emissions and need to be monitored to protect people on their passage through the tunnel from danger and impacts on their health. Accidents in tunnels, and particularly fires, can have dramatic consequences and can prove extremely costly in terms of human life, increased congestion, pollution and repair costs. At every time people in the tunnel need to be supplied with breathable air and sufficient visibility. Since 1990 JES Elektrotechnik GmbH develops, installs and maintains systems to monitor air characteristics and lighting conditions in tunnels. Our systems are robust, durable and resistant against the corrosive atmosphere in a tunnel. They operate reliably and have a high accuracy in measurement. All systems fulfil the requirements of the EC guideline 2004/54/EC (Minimum safety requirements for tunnels in the trans-European road network) and the more detailed national guidelines and provisions:
Our range of products for tunnel covers systems for monitoring of
|
Air flow measurement | |
---|---|
Type | JES t/FL-USX |
Measuring method | Determination of direction dependant differential transi-tion times of ultrasonic pulses |
Measured values | Air speed Air flow rate Direction of air flow Air temperature |
Measuring range | -40 .. 40 m/s |
Resolution | 0.1 m/s, accuracy depending on measuring distance, flow profile, installation, typically <±0.2 m/s at 3 m/s |
Response time | > 1s … 180 s, configurable |
Measurement path length | 1.2 - 25 m |
Alignment | 30 - 60° to tunnel longitudinal axis, typically 45° |
Outputs | |
---|---|
Analogue output | 1 x 4-20 mA, 400 Ω, isolated can be assigned any measured value and output range |
Output range | configurable, typically: -20 to 20 m/s |
Relay contacts | 1 x fault indication (NC) 1 x direction of air flow (NC) (max. 48 V / 0.5 A) |
Digital interfaces | 1x RS 485 MODBUS RTU to control system, bidirectional 1x Intercom RS 485 master-slave |
Terminal box A - JES t/FL-USX-TBX-A | ||
---|---|---|
Type | t/FL-USX-TBX-A | |
System cable port | 1 (for D-FL 220 T M Sensor A) | |
Power supply | 100 to 240 VAC, 50/60 Hz | |
Supply voltage fluctuations | ± 10 % | |
Overvoltage category | II | |
Power rating | 60 W | |
Appliance class | Class I | |
Material | Stainless steel 1.4404 (AISI 316L) | |
Mounting | incl. mounting clamp made from Stainless steel 1.4404 for wall mounting | |
IP rating | IP 69 | |
Dimensions | 250 x 160 x 110 mm | |
Weight | approx. 3.2 kg | |
Indoor/Outdoor use | Indoor use (tunnel) | |
Altitude | up to 2,000 m | |
Temperature range | -40 .. +60 °C | |
Humidity range | 0 .. 100% relative humidity (non-condensing) | |
Pollution degree | 4 (intended environment) / 2 (when cover removed) |
Terminal box B - t/FL-USX-TBX-B | ||
---|---|---|
Type | t/FL-USX-TBX-B | |
System cable port | 1 (for D-FL 220 T M Sensor B) | |
Power supply | 24 VDC ±10 % | |
Current rating | 1 A | |
Appliance class | Class III | |
Material | Stainless steel 1.4404 (AISI 316L) | |
Mounting | incl. mounting clamp made from Stainless steel 1.4404 for wall mounting | |
IP rating | IP 69 | |
Dimensions | 160 x 160 x 110 mm | |
Weight | approx. 1.9 kg | |
Indoor/Outdoor use | Indoor use (tunnel) | |
Temperature range | -40 .. +60 °C | |
Humidity range | 0 .. 100% relative humidity (non-condensing) | |
Pollution degree | 4 (intended environment) / 2 (when cover removed) |
smart/Architecture gateway for t/FL-USX - smart/BOX-S-FL-USX | ||
---|---|---|
Type | smart/BOX-S-FL-USX | |
System cable port | 1 (for D-FL 220 T M sensor) | |
Power supply | 100 to 240 VAC, 50/60 Hz | |
Supply voltage fluctuations | ± 10 % | |
Overvoltage category | II | |
Power rating | 60 W | |
Appliance class | Class I | |
Digital interfaces | MODBUS RTU (RS-485) MODBUS/TCP (Ethernet) Webserver for configuration (Ethernet) |
|
Material | Stainless steel 1.4404 (AISI 316L) | |
Mounting | incl. mounting clamp made from Stainless steel 1.4404 for wall mounting | |
IP rating | IP 69 | |
Dimensions | 250 x 160 x 110 mm | |
Weight | approx. 3.2 kg | |
Indoor/Outdoor use | Indoor use (tunnel) | |
Altitude | up to 2,000 m | |
Temperature range | -40 .. +60 °C | |
Humidity range | 0 .. 100% relative humidity (non-condensing) | |
Pollution degree | 4 (intended environment) / 2 (when cover removed) |