User Tools

Site Tools


en:datasheets:smartecs

PDF


JES smart/ECS Multi Gas Sensor

Features

  • Smart IoT enabled gas sensor
  • Up to 4 electrochemical gas sensor modules (CO, NO, NO2, SO2)
  • Installation in-situ (in the tunnel’s driving area) or with suction line adapter
  • Stainless steel housing 1.4404 (AISI 316L)
  • IP rating IP69K
  • Connection to tunnel control system by
    • MODBUS RTU (RS-485)
    • MODBUS/TCP (Ethernet)
    • Analogue and relay outputs
    • JSON Web service (Ethernet)
  • Integrated web server for visualisation, configuration, data logging, remote maintenance (Ethernet option only)
  • Optional smart/HUB IoT operating and control unit with touch display
  • Plug & play operation

System setup

  • smart/ECS sensor to be mounted either
    • in-situ (directly in the tunnel’s driving area) or
    • extractive in a niche, cross-cut, etc.
  • Optional smart/HUB with touch display

Operation

Gas monitoring during normal operation is used to control the tunnel ventilation at normal operation. If and with how much power artificial ventilation by jet fans is operated depends on the measured visibility and gas concentration. Electrochemical gas sensor cells induce currents proportional to the prevailing gas concentration. With these currents and the measured temperature, the gas sensor modules calculate the gas concentrations.

Advantanges

  • Specifically designed for application in tunnels
  • Single sensor instead of transmitter/receiver pair requiring exact alignment
  • Low maintenance requirements, stable, accurate
  • Pre-calibrated gas sensor modules for easy exchange
  • Smart IoT enabled solution from sensor over hub to asset management
  • Condition monitoring
  • Remote maintenance
  • Flexible integration into tunnel control system

Application

Tunnels are important infrastructure elements in road networks and facilitate the connection of regions.

Environmental conditions in tunnels are influenced by fog, particles and emissions and need to be monitored to protect people on their passage through the tunnel from danger and impacts on their health. Accidents in tunnels, and particularly fires, can have dramatic consequences and can prove extremely costly in terms of human life, increased congestion, pollution and repair costs. At every time people in the tunnel need to be supplied with breathable air and sufficient visibility.

Since 1990 JES Elektrotechnik GmbH develops, installs and maintains systems to monitor air characteristics and lighting conditions in tunnels. Our systems are robust, durable and resistant against the corrosive atmosphere in a tunnel. They operate reliably and have a high accuracy in measurement.

All systems fulfil the requirements of the EC guideline 2004/54/EC (Minimum safety requirements for tunnels in the trans-European road network) and the more detailed national guidelines and provisions:

  • Austria: RVS 09.02 Tunnelausrüstung
  • Germany: RABT Richtlinien für die Ausstattung und den Betrieb von Straßentunneln
  • Switzerland: ASTRA Richtlinien und Fachhandbuch Betriebs- und Sicherheitsausrüstungen (BSA)

Our range of products for tunnel covers systems for monitoring of

  • Visibility (extractive or in-situ)
  • Toxic gases like CO, NO, NO2 (extractive or in-situ)
  • Air velocity, direction and temperature
  • Luminance (access, threshold and interior zone)
  • Illuminance


Technical Specifications

Sensor device

Sensor device smart/ECS (SH3 / WH3 housing option)
Type smart/ECS
Gas sensor ports up to 3 (to be specified on order)
Power supply 24 VDC ± 10 %
Current consumption max. 300 mA (@ 24 VDC)
Appliance class Class III (PELV)
Material Stainless steel 1.4404 (AISI 316L)
IP rating IP 69
Dimensions 160 x 160 x 100 mm
Weight Approx. 2.5 Kg
Digital interfaces
(standard)
MODBUS RTU (RS-485)
MODBUS/TCP (Ethernet)
Webserver for configuration (Ethernet)
Analogue/relay outputs (optional) up to 2 analogue / relay output modules, each:
3 x 4 – 20 mA (2-wire, active)
3 x SPST-NO (max. 60 VDC / 25 VAC, max. 0.5 A)
Temperature range -40 .. +60 °C
Pressure range 900 .. 1100 hPa
Humidity range 15 .. 95% relative humidity (non-condensing)
Storage temperature -40 .. +85 °C (without gas sensor modules)


Sensor device smart/ECS (SH4 / WH4 housing option)
Type smart/ECS
Gas sensor ports up to 4 (to be specified on order)
Power supply (Standard) 24 VDC ± 10 %
Power supply (IPS option) 100 to 240 VAC, 50/60 Hz
Supply voltage fluctuations (IPS option) ± 10 %
Current consumption max. 300 mA (@ 24 VDC)
Appliance class Class III (PELV)
Class I (IPS option)
Material Stainless steel 1.4404 (AISI 316L)
IP rating IP 69
Dimensions 250 x 160 x 100 mm
Weight Approx. 2.5 Kg
Digital interfaces
(standard)
MODBUS RTU (RS-485)
MODBUS/TCP (Ethernet)
Webserver for configuration (Ethernet)
Analogue/relay outputs (optional) up to 2 analogue / relay output modules, each:
3 x 4 – 20 mA (2-wire, active)
3 x SPST-NO (max. 60 VDC / 25 VAC, max. 0.5 A)
Indoor/Outdoor use Indoor use (tunnel)
Altitude (IPS option only) up to 2,000 m
Temperature range -40 .. +60 °C
Pressure range 900 .. 1100 hPa
Humidity range 15 .. 95% relative humidity (non-condensing)
Storage temperature -40 .. +85 °C (without gas sensor modules)
Pollution degree (IPS option only) 4 (intended environment) / 2 (when cover removed)


Gas sensor modules

Gas sensor module CO-500
Type smart/ECS-CO-500
Measuring method Electrochemical cell
Measured value Gas concentration in ppm
Measuring range Configurable within 0 .. 500 ppm CO
typically 0 .. 300 ppm CO
Maximum overload 1,000 ppm CO
Lower detectable limit < 0.5 ppm CO
Resolution 0.1 ppm CO
Accuracy ± 2 ppm or 2 % reading1)
Temperature compensation yes
T90 time < 40 s
Long term drift < 2 % signal loss per month
Dimensions ∅ 38 x 74 mm
Weight 88 g
Expected operation life 3 years in air
Storage life 6 months in packaging
Storage temperature 5 .. 20 °C

Gas sensor module NO2-2
Type smart/ECS-NO2-2
Measuring method Electrochemical cell
Measured value Gas concentration in ppm
Measuring range Configurable within 0 .. 2 ppm NO2
typically 0 .. 2 ppm NO2
Maximum overload 10 ppm NO2
Lower detectable limit 0.05 ppm NO2
Resolution 0.02 ppm NO2
Accuracy ± 0.05 ppm or 5 % reading2)
Temperature compensation yes
T90 time < 60 s
Long term drift < 2 % signal loss per month
Dimensions ∅ 38 x 74 mm
Weight 88 g
Expected operation life 2 years in air
Storage life 6 months in packaging
Storage temperature 5 .. 20 °C


Gas sensor module NO2-20
Type smart/ECS-NO2-20
Measuring method Electrochemical cell
Measured value Gas concentration in ppm
Measuring range Configurable within 0 .. 20 ppm NO2
typically 0 .. 10 ppm NO2
Maximum overload 200 ppm NO2
Lower detectable limit < 0.15 ppm NO2
Resolution 0.05 ppm NO2
Accuracy ± 0.5 ppm or 2 % reading3)
Temperature compensation yes
T90 time < 60 s
Long term drift < 2 % signal loss per month
Dimensions ∅ 38 x 74 mm
Weight 88 g
Expected operation life 2 years in air
Storage life 6 months in packaging
Storage temperature 5 .. 20 °C

Gas sensor module NO-100
Type smart/ECS-NO-100
Measuring method Electrochemical cell
Measured value Gas concentration in ppm
Measuring range Configurable within 0 .. 100 ppm NO
typically 0 .. 30 ppm NO
Maximum overload 200 ppm NO
Lower detectable limit 1 ppm NO
Resolution 0.05 ppm NO
Accuracy ± 0.5 ppm or 2 % reading4)
Temperature compensation yes
T90 time < 10 s
Long term drift < 2 % signal loss per month
Dimensions ∅ 38 x 74 mm
Weight 88 g
Expected operation life 3 years in air
Storage life 6 months in packaging
Storage temperature 5 .. 20 °C


Gas sensor module NO-25
Type smart/ECS-NO-25
Measuring method Electrochemical cell
Measured value Gas concentration in ppm
Measuring range Configurable within 0 .. 25 ppm NO
overload up to 0 .. 30 ppm NO
Maximum overload 50 ppm NO
Lower detectable limit < 0.4 ppm NO
Resolution 0.05 ppm NO
Accuracy ± 0.2 ppm or 2 % reading5)
Temperature compensation yes
T90 time < 10 s
Long term drift < 2 % signal loss per month
Dimensions ∅ 38 x 74 mm
Weight 88 g
Expected operation life 3 years in air
Storage life 6 months in packaging
Storage temperature 5 .. 20 °C

Gas sensor module SO2-CF20
Typ smart/ECS-SO2-CF20
Measuring method Electrochemical cell
Measured value Gas concentration in ppm
Measuring range 0 - 30 ppm SO2
Maximum overload 100 ppm SO2
Resolution < 0.1 ppm SO2
Accuracy < 2 % measurement value
Inboard Filter To remove effect from H2S and HCl (cross sensitivity)
T90 time < 30 s
Long term drift < 2 % signal loss per month
Dimensions ∅ 38 x 74 mm
Weight 88 g
Expected operation life 2 years in air
Storage life 6 months in packaging
Storage temperature 5 … 20 °C


Analogue / relay output module

Analogue / relay output module ARO
Type smart/CORE-ARO
Analogue outputs 3 x 4 - 20 mA
Analogue output type 2-wire, active
Relay outputs 3 x SPST-NO
Max. contact rating max. 60 VDC / 25 VAC, max. 0.5 A

2.4" Touch display

2.4“ Internal touch display D2
Type smart/CORE-D2
Display type TFT colour
Diagonal screen size 2.4” (60.96 mm)
Display area 49.96 x 37.72 mm
Resolution 320 x 240 px
Touch type capacitive
Backlight LED - white

Temperature sensor option

smart/ECS-TMP Temperature sensor option
Type smart/ECS-TMP
Temperature sensor Pt1000 DIN B, R0: 1000 Ω, Temperature coefficient: 3.850 x 10-3/°C, Standard: DIN EN 60751
Sensor sleeve material Stainless steel 1.4571 (AISI 316Ti)
Cable material Silicon
IP rating IP 67
Cable length 30 cm (longer on request)
Temperature range -60 .. +180 °C
Humidity range 5 .. 95% relative humidity (non-condensing)
Storage temperature -30 .. +70 °C


Temperature and humidity sensor

Temperature and humidity sensor
Type smart/CORE-TRH
Measured values Temperature, Relative humidity
Calculated variables Dew point, Frost point, Wet bulb temperature, Ice bulb temperature, Water vapour partial pressure, Mixture ratio, Absolute humidity, Specific enthalpy
Measuring ranges Temperature: -40 .. 80 °C
Relative humidity: 0 .. 100 %
Accuracy Temperature: ±(0,2 °C + 0,67 % * abs (reading - 20 °C))
Relative humidity:
-15 .. 40 °C: ± (1.3 + 0.3 % reading) %RH for RH ≤ 90 %, ± 2.3 % %RH for RH > 90 %
-40 .. 80 °C: ± (1.5 + 1.5 % reading) %RH
Resolution Temperature: 0.01 °C
Relative humidity: 0.01 %RH
T90 time < 15 s with stainless steel grid filter at 20 °C
Current consumption 3 mA
Housing material Stainless steel 1.4404 (AISI 316L)

Conformities

Conformities
Markings
Electrical standards 2014/35/EU Low Voltage Directive (LVD)
2014/30/EU Electromagnetic compatibility (EMC)
EN IEC 61000-6-2:2019 Immunity standard for industrial environments
EN IEC 61000-6-3:2007 + A1: 2011 Emission standard for residential, commercial and light-industrial environments
EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use
EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements
Tunnel safety standards Austria: RVS 09.02.22
Germany: RABT 2006
Switzerland: ASTRA RL 13001, Fachhandbuch BSA
Norway: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels
International: ISO 23431 Measurement of road tunnel air quality
Gas monitoring Europe: EN 50545-1
Austria: ÖNORM M9419
Germany: VDI 2053

1) , 2) , 3) , 4) , 5)
whichever is greater
en/datasheets/smartecs.txt · Last modified: 2024-12-05 11:10 by jesadmin